Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
05/15/2014
Applicant:
COMPLETE FIRE PROTECTION INC
Description:
INSTALL 566 NEW FIRE SPRINKLERS
Contractors:
  • COMPLETE FIRE PROTECTION INC

Outstanding Activity Conditions

Permit Number - T14BU00509
Permit Status: Final
Permit Description: INSTALL 566 NEW FIRE SPRINKLERS
Total Outstanding Activity Conditions - 1
Date Name
05/15/2014 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T14BU00509
Permit Description: INSTALL 566 NEW FIRE SPRINKLERS
Total Completed Inspections - 2
Date Description Inspector Results Comments
07/21/2014 FIRE SPKLR - OH PIPING & HYDRO CSCHULTZ Approved OH 200 psi 2 hours Approved
Placement need to correct some areas noted on plans -
09/23/2014 FIRE SPKLR - FINAL CBASALDUA Approved 1. Water Flow #1 30 sec.
2. Water Flow #2 39 sec.
3. Main Drain # 1 70/55/70.
4. Main Drain #2 75/50/75.

Documents

File Name Document Type  
001_SPRINKLER.TIF FIRE PLANS VIEW
002_SPRINKLER.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW