Permit: T13CM07241
Permit Details
Apply Date:
12/02/2013
Applicant:
ALFONSO MARTINEZ
Description:
UPDATE ELECTRICAL BOX
Permit Reviews
Permit Number - T13CM07241
Permit Status: Expired
Permit Description: UPDATE ELECTRICAL BOX
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 12/02/2013 | RESIDENTIAL - BLDG/WWM | 12/02/2013 | ACTIVE |
Outstanding Activity Conditions
Permit Number - T13CM07241
Permit Status: Expired
Permit Description: UPDATE ELECTRICAL BOX
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/02/2013 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T13CM07241
Permite Description: UPDATE ELECTRICAL BOX
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2013 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | 1. USE APPROVED GROUND ROD CLAMP AT FIRST ROD 2. BOND WATER & GAS 3. ADDRESS LABEL ON SERVICE 4. ROOF JACK & APPROVED RISER CONDUIT SUPPORTS 5. USE APPROVED CONDUIT FITTINGS FOR OUTSIDE USE - (RAIN TITE) |
| 12/05/2013 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |