REPLACE 3 TON ROOF MOUNT HVAC
Contractors:
- ALASKAN HOME SERVICES INC
Outstanding Activity Conditions
Permit Number - T13CM04390
Permit Status: Expired
Permit Description: REPLACE 3 TON ROOF MOUNT HVAC
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 07/18/2013 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T13CM04390
Permite Description: REPLACE 3 TON ROOF MOUNT HVAC
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2014 | MECHANICAL - INTERMEDIATE | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
| 01/31/2014 | MECHANICAL - FINAL | N/A | Denied | 1. WHITE WIRE NOT TO BE USED AS HOT LEG 2. MINIMUM 3" ON SEDIMENT TRAP 3. DUCT JOINT SEALANT NOT AN APPROVED METHOD FOR SEALING ROOF JACK (A/C CURB). PROVIDE APPROVED MATERIAL 4. DOUBLE LUGGING NOT PERMITTED. LAND GROUND WIRE AT PANEL ON SEPARATE GROUND LUG |
| 01/31/2014 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |