Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
3003 N EDITH BL
Address NEW:
3003 N EDITH BL
Apply Date:
06/28/2013
Applicant:
ALASKAN HOME SERVICES INC
Description:
REPLACE 2 TON SPLIT SYSTEM
Contractors:
  • ALASKAN HOME SERVICES INC

Outstanding Activity Conditions

Permit Number - T13CM03980
Permit Status: Expired
Permit Description: REPLACE 2 TON SPLIT SYSTEM
Total Outstanding Activity Conditions - 1
Date Name
06/28/2013 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T13CM03980
Permite Description: REPLACE 2 TON SPLIT SYSTEM
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
07/02/2013 MECHANICAL - INTERMEDIATE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/02/2013 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/02/2013 MECHANICAL - FINAL N/A Denied PROVIDE THE REQUIRED SERVICE RECEPTACLE ON THE ROOF FOR A NEW A/C INSTALLATION. TERMINATE CONDENSATE TO AN APPROVED LOCATION. ADD A STAND PIPE IN VENT ON CONDENSATE DRAIN.
ELEC CORDS CANNOT CROSS AGAINST FURNACE VENT. PROVIDE 6" CLEARANCE