Permit: T12OT00640
Permit Details
Apply Date:
04/19/2012
Applicant:
ADDISIGNS
Description:
SIGN 20426
Contractors:
- ADDISIGNS
Outstanding Inspections
Permit Status: Expired
Permit Number: T12OT00640
Permite Description: SIGN 20426
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2012 | SIGN ELECTRIC | N/A | Partial Approval | PROVIDE PROPER MARKINGS OF THE FUSE BOX AND VERIFY THAT THE CIRCUIT IS ONLY BEING UTILIZED FOR THE SIGNS. |
| 12/05/2012 | SIGN INSPECTION | N/A | Denied | THE SIGN SETBACK AND THE HEIGHT OF SIGN DOES NOT MEET THE MINIMUM REQUIREMENTS. THE SETBACK IS SUPPOSE TO BE 36 FEET AND IS AT 35.75. THE TOP OF SIGN HEIGHT IS LISTED AT 10 FEET ABOVE THE ADJACENT ROADWAY GRADE WHICH IS APPROXIMATELY 3 FEET TOO HIGH DUE TO THE INCLINE OF THE SHOULDER. THIS WILL NEED TO BE CHECKED FURTHER TO DETERMINE HOW THE SIGN WILL HAVE TO BE CHANGED TO MEET THE CODE REQUIREMENTS. THE SIGN ADMINISTRATOR GLENN MOYER HAS ADVISED THE CONTRACTOR THAT HE IS ALLOWED TO USE THE LOWEST POINT WITHIN 20 OF THE EXISTING SIGN POLE TO BE UTILIZED AS THE GRADE REFERANCE POINT. IT APPEARS THAT THIS POINT WILL STILL REQUIRE THE SIGN HEIGHT TO BE MODIFIED TOO BRING THE SIGN INTO COMPLIANCE. |
Completed Inspections
Permit Status: Expired
Permit Number: T12OT00640
Permit Description: SIGN 20426
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/27/2012 | SIGN SITE REVIEW | MRUSSO | Approved | |
| 06/14/2012 | SIGN EXCAVATION | MRUSSO | Approved |