Permit: T12CM02477
Permit Details
Apply Date:
05/07/2012
Applicant:
RAMIOR GONZALES ROSIN
Description:
RECONNECT ELECTRIC; DUPLX
Outstanding Activity Conditions
Permit Number - T12CM02477
Permit Status: Final
Permit Description: RECONNECT ELECTRIC; DUPLX
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/07/2012 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T12CM02477
Permit Description: RECONNECT ELECTRIC; DUPLX
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2012 | ELECTRIC - FINAL | DSANTACR | Approved | IVRS - Inspection :* |
| 05/08/2012 | ELECTRIC - RECONNECT | DSANTACR | Approved | IVRS - Inspection :* |
| 05/09/2012 | TEP CLEARANCE - AM | JWEATHER | Approved | RECN CLEARED FOR 6928 & 6930 S. 6TH AVE PER D. SANTACRUZ |
| 05/09/2012 | PERMIT FINALED | JWEATHER | Approved |