Permit: T12BU01240
Permit Details
Apply Date:
10/19/2012
Applicant:
ROCHE CONSTRUCTORS INC ,
Description:
Install 35 ' of 8" fire service underground
Contractors:
- ROCHE CONSTRUCTORS INC ,
Outstanding Activity Conditions
Permit Number - T12BU01240
Permit Status: Final
Permit Description: Install 35 ' of 8" fire service underground
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
10/19/2012 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T12BU01240
Permit Description: Install 35 ' of 8" fire service underground
Total Completed Inspections - 3
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/29/2012 | FIRE SPKLR - UG, PIPING, HYDRO | CSCHULTZ | Approved | Tested for 2 hours at 200 PSI, no leaks noticed all torque mega lug nuts broken off and PVC plastic wrap was around the backside of pipe and ready to wrap all fire sprinkler ductile pipe. Okay to cover with clean dirt. |
12/05/2012 | FIRE SPKLR - FINAL | CSCHULTZ | Approved | |
12/05/2012 | FIRE SPKLR - UG PIPING FLUSH | CSCHULTZ | Approved | FLUSHED FOR 1 MIN |