Permit: T12BU01074
Permit Details
Apply Date:
09/13/2012
Applicant:
ALLAN FIRE PROTECTION SYSTEMS
Description:
Install 98 fire sprinklers & 95" of 4" underground piping
Contractors:
- ALLAN FIRE PROTECTION SYSTEMS
Outstanding Activity Conditions
Permit Number - T12BU01074
Permit Status: Final
Permit Description: Install 98 fire sprinklers & 95" of 4" underground piping
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/13/2012 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T12BU01074
Permit Description: Install 98 fire sprinklers & 95" of 4" underground piping
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/18/2012 | FIRE SPKLR - UG, PIPING, HYDRO | CSCHULTZ | Approved | |
| 09/19/2012 | FIRE SPKLR - UG PIPING FLUSH | CSCHULTZ | Approved | FLUSHED FOR 5 MINS WATER CLEANER JUST A LITE RUST COLOR. |
| 09/24/2012 | FIRE SPKLR - OH PIPING & HYDRO | CSCHULTZ | Approved | 200 psi for 2 hours - checked bolts for tap on underground pipe to riser. Need to check upright coverage around hood exhaust duct work, was not installed at time of OH psi check. |
| 10/23/2012 | FIRE SPKLR - FINAL | CSCHULTZ | Approved | 70-60-70 |