Permit: T12BU00648
Permit Details
Apply Date:
05/22/2012
Applicant:
SIMPLEX GRINNELL L P
Description:
FIRE ALARM
Contractors:
- SIMPLEX GRINNELL L P
Outstanding Activity Conditions
Permit Number - T12BU00648
Permit Status: Closed
Permit Description: FIRE ALARM
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/22/2012 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Closed
Permit Number: T12BU00648
Permit Description: FIRE ALARM
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/28/2012 | FIRE - ALARM FINAL | CSCHULTZ | Approved | 1.) Manual pull box station located by room 154 is loose and pulling out of the wall need the correct. 2.) In the grand ballroom restroom flow switch is greater than 3 mins. before alarm activated need to correct to 3- to 60 seconds. 3.) 2nd floor meeting room's inspector test valve can not be opened need to correct. 4.) Flow switch on the 7th floor set off at 13 sec. to soon need to correct at 30 to 60 seconds. 5.) Flow switch on the 2nd floor greater than 3 mins before alarm activated need to correct to 30 to 60 seconds. 6.) Main tamper switch for the riser buffer fly valve not monitored need to monitor this valve. 7.) Need locks on all breakers for FACP and power boosters. |