Permit: T12BU00410
Permit Details
Apply Date:
03/29/2012
Applicant:
UNITED FIRE EQUIPMENT CO. **APA**
Description:
KITCHEN EXHAUST HOOD
Contractors:
- UNITED FIRE EQUIPMENT CO. **APA**
Permit Reviews
Permit Number - T12BU00410
Permit Status: Expired
Permit Description: KITCHEN EXHAUST HOOD
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/29/2012 | MECHANICAL | 03/29/2012 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T12BU00410
Permit Status: Expired
Permit Description: KITCHEN EXHAUST HOOD
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/29/2012 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T12BU00410
Permite Description: KITCHEN EXHAUST HOOD
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| FIRE - KITCHEN EXH HOOD FINAL | N/A | Not Inspected | ||
| 04/02/2012 | MECHANICAL - FINAL | N/A | Not ready for Inspection | IVRS - Inspection :* 1. EQUIPMENT DOES NOT FIT UNDER HOODS 2. CHAR HOOD HAS BEEN MODIFIED, NOT LIQUID TIGHT AT TOP OF HOOD 3. GREASE DUCT IS TO BE WELDED TO HOOD 4. GAS CONVECTION OVEN (3) UNDER TYPE 2 HOODS 5. GRIDDLE (GAS) UNDER TYPE 2 HOOD |