Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address NEW:
101 E PENNINGTON ST
Apply Date:
03/26/2012
Applicant:
CUTLER FIRE PROTECTION INC ,
Description:
Install 15' of 4" underground & 122 fire sprinklers
Contractors:
  • CUTLER FIRE PROTECTION INC ,

Outstanding Activity Conditions

Permit Number - T12BU00395
Permit Status: Final
Permit Description: Install 15' of 4" underground & 122 fire sprinklers
Total Outstanding Activity Conditions - 1
Date Name
03/26/2012 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T12BU00395
Permit Description: Install 15' of 4" underground & 122 fire sprinklers
Total Completed Inspections - 4
Date Description Inspector Results Comments
05/30/2012 FIRE SPKLR - UG, PIPING, HYDRO CSCHULTZ Approved 200 PSI FOR 2 HOURS
05/30/2012 FIRE SPKLR - UG PIPING FLUSH CSCHULTZ Approved FLUSHED FOR 1 MIN
07/31/2012 FIRE SPKLR - FINAL CSCHULTZ Approved Needed to reinstall cover caps on pendent sprinkler heads on the 2 floor apartments both uprights and pendents are exposed to each other. Final will be given when ceiling is replaced. Okay to use 1st floor and basement.
07/31/2012 FIRE SPKLR - OH PIPING & HYDRO CSCHULTZ Approved All corretion are done

Documents

File Name Document Type  
001_SPRINKLER.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW