Permit: T11PL01317
Permit Details
Apply Date:
08/08/2011
Applicant:
PLUMB PLUMBING, LLC *APA*
Description:
REPLACE GAS LINE and WATER HEATER
Contractors:
- PLUMB PLUMBING LLC
- PLUMB PLUMBING, LLC *APA*
Permit Reviews
Permit Number - T11PL01317
Permit Status: Final
Permit Description: REPLACE GAS LINE and WATER HEATER
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 08/08/2011 | PLUMBING | 08/08/2011 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T11PL01317
Permit Status: Final
Permit Description: REPLACE GAS LINE and WATER HEATER
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/08/2011 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T11PL01317
Permit Description: REPLACE GAS LINE and WATER HEATER
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2011 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection :* 1) WATER SERVICE REPAIRED/REPLACED OK 2) WATER HEATER INSTALLED OK 3) GAS PRESSURE TEST OK 4) ROOF TOP UNIT INSTALLED WITHOUT PERMITS, APPEARS REASONABLY SAFE 5) PAINT CONDENSATE DRAIN 6) DUCT REQUIRES 2" INSULATION-INSTALLED IS 1" 7) LABEL UNIT IN ELECTRIC BOX DISCONNECT |
| 08/17/2011 | PLUMBING - GAS PRESSURE TEST | RMYERS | Approved | IVRS - Inspection :* |
| 08/19/2011 | PERMIT FINALED | JWEATHER | Approved |