Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Withdrwn
Type:
SIGN PERMIT
Apply Date:
12/20/2011
Applicant:
DOUBLE T SIGNS INC
Description:
SIGN 20134 (3 ILLUM. WALL SIGNS)
Contractors:
  • DOUBLE T SIGNS INC

Outstanding Inspections

Permit Status: Withdrwn
Permit Number: T11OT02316
Permite Description: SIGN 20134 (3 ILLUM. WALL SIGNS)
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
03/06/2012 SIGN SHOP N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/06/2012 SIGN ELECTRIC N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) A MARKING LABEL IS NEEDED 600.4
2) FULL ISOLATE POWER-NEED JUNCTION BOX COVER AND CONNECTOR
3) SHEET METAL THREAD SCREWS NOT ALLOWED FOR GROUNDING
4) MAINTAIN GTO SEPERATIONS AND CLEARANCES
03/07/2012 SIGN INSPECTION N/A Denied DENIED, NO PAPERWORK ON SITE

Completed Inspections

Permit Status: Withdrwn
Permit Number: T11OT02316
Permit Description: SIGN 20134 (3 ILLUM. WALL SIGNS)
Total Completed Inspections - 1
Date Description Inspector Results Comments
12/22/2011 SIGN SITE REVIEW ACONNOR Approved