Permit: T11ME00244
Permit Details
Apply Date:
08/31/2011
Applicant:
DEWOODY'S HEATING AND AIR CONDIT *APA*
Description:
REPLACE:31/2 TON SPLIT SYSTEM HEAT PUMP
Contractors:
- DEWOODY'S HEATING AND AIR CONDIT *APA*
Outstanding Activity Conditions
Permit Number - T11ME00244
Permit Status: Expired
Permit Description: REPLACE:31/2 TON SPLIT SYSTEM HEAT PUMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/31/2011 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T11ME00244
Permite Description: REPLACE:31/2 TON SPLIT SYSTEM HEAT PUMP
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/03/2012 | MECHANICAL - FINAL | N/A | Partial Approval | IVRS - Inspection :* 1) PVC CONDENSATE NOT SUPPORTED UNDER HOUSE 2) ALL PVC PIPE AND FITTINGS ARE TO HAVE PRIMER, PRIMER IS TO BE PURPLE IN COLOR AND APPLIED PRIOR TO GLUE REMOVE AND REPLACE ALL UN-PRIMERED FITTINGS 3) INDOOR UNIT IS OVER FUSED |
Completed Inspections
Permit Status: Expired
Permit Number: T11ME00244
Permit Description: REPLACE:31/2 TON SPLIT SYSTEM HEAT PUMP
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/03/2012 | MECHANICAL - INTERMEDIATE | MRAMBER | Approved | IVRS - Inspection :* |