Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T11CM01688
Permit Details
Apply Date:
06/01/2011
Applicant:
ORANGUTAN HOME SERVICES, INC *APA*
Description:
REPLACE; 5 TON GROUND-MOUNT SPLIT SYSTEM (APA)
Contractors:
- ORANGUTAN HOME SERVICES, INC *APA*
Outstanding Activity Conditions
Permit Number - T11CM01688
Permit Status: Expired
Permit Description: REPLACE; 5 TON GROUND-MOUNT SPLIT SYSTEM (APA)
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
06/01/2011 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T11CM01688
Permite Description: REPLACE; 5 TON GROUND-MOUNT SPLIT SYSTEM (APA)
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
MECHANICAL - INTERMEDIATE | N/A | Not Inspected | ||
MECHANICAL - FINAL | N/A | Not Inspected |