Permit: T11BU01718
Permit Details
Apply Date:
12/28/2011
Applicant:
SUN DEVIL FIRE EQUIPMENT INC , *APA*
Description:
INSTALL:FIRE SUPPRESSION SYSTEM
Contractors:
- SUN DEVIL FIRE EQUIPMENT INC , *APA*
Permit Reviews
Permit Number - T11BU01718
Permit Status: Expired
Permit Description: INSTALL:FIRE SUPPRESSION SYSTEM
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 12/28/2011 | MECHANICAL | 12/28/2011 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T11BU01718
Permit Status: Expired
Permit Description: INSTALL:FIRE SUPPRESSION SYSTEM
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/28/2011 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T11BU01718
Permite Description: INSTALL:FIRE SUPPRESSION SYSTEM
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| PERMIT FINALED | N/A | Not Inspected | ||
| 01/25/2012 | FIRE - KITCHEN EXH HOOD FINAL | N/A | Denied | All electrical under hood and pulled in from the outside and using under the hood shall shut off when hood extinguisher system has activated, three outlets need to shut down. Exhaust fan shall stay on when extinguisher system has activated. |
Completed Inspections
Permit Status: Expired
Permit Number: T11BU01718
Permit Description: INSTALL:FIRE SUPPRESSION SYSTEM
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2011 | MECHANICAL - FINAL | LHANLY | Approved |