Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
2402 S PARK AV #01
Apply Date:
02/14/2011
Applicant:
REX, CATHERINE APPLEGATE
Description:
BUILDING INVESTIGATION
Architects:
  • REX, CATHERINE APPLEGATE

Permit Reviews

Permit Number - T11BU00214
Permit Status: Expired
Permit Description: BUILDING INVESTIGATION
Start Date Submittal Complete Date Status  
02/14/2011 OTHER 02/14/2011 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T11BU00214
Permit Status: Expired
Permit Description: BUILDING INVESTIGATION
Total Outstanding Activity Conditions - 1
Date Name
02/14/2011 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T11BU00214
Permite Description: BUILDING INVESTIGATION
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
02/15/2011 BUILDING - FINAL N/A Denied 1) SOUTH YARD IS BEING PAVED WITHOUT PERMITS. DESIGNATED ACCESSIBLE PARKING IS NON COMPLIANT WITH ANSI 117.1 WHICH WILL REQUIRE RELOCATION OF SPACE AND ALTERNATE STRIPING.

2) RAFTER TAILS OF MAIN STRUCTURE SHOW SERIOUS SIGNS OF ROT THAT APPEARS TO EXTEND INTO THE BUILDING. A REGISTERED ENGINEER WILL NEED TO EVALUATE STRUCTURAL INTEGRITY OF ROOF.

3) UPPER COMBUSTION AIR REQUIRED FOR MECHANICAL ROOM ON SOUTH SIDE OF BUILDING. GRAVITY VENTS IN SAME ROOM REQUIRE 3" CLEAR TO WOOD.

4) THERE ARE NON COMPLIANT PLUMBING DRAIN SYSTEMS OUTSIDE THE BUILDING AT THE SOUTH WEST CORNER. IMPROPER CONFIGURATIONS; IMPROPER BURIAL; OTHER CODE VIOLATIONS. ALL WORK DONE WITHOUT PERMITS.

5) ELECTRIC PANEL HAS MISMATCHED BREAKERS THAT DO NOT CONFORM TO PANEL TYPE. PANEL SCHEDULE IS MISSING, BREAKER RATINGS ARE ILLEGIBLE.

6) ACCESSIBILITY REQUIREMENTS MUST BE MET FOR COMMERCIAL PROPERTY. DOOR HARDWARE AND THRESHOLDS ARE CURRENTLY OUT OF COMPLINACE.

7) PVC PLUMBING HAS BEEN USED INSIDE THE BUILDING IN VIOLATION OF THE PLUMBING CODES (WATER SUPPLY TO SINK ON NORTH SIDE)

8) ART ROOM SINK HAS BEEN INSTALLED WITHOUT PERMITS AND DOES NOT MEET BUILDING CODE REQUIREMENTS.

9) KITCHEN HAS BEEN RELOCATED FROM CENTER OF BUILDING TO EAST SIDE WITHOUT PERMITS.

10) SINK IN BABY ROOM INSTALLED WITHOUT PERMITS AND IN VIOLATION OF PLUMBING CODES.

11) FURNACE IN HALL WAY HAS BEEN HAZARDOUSLY INSTALLED. COMBUSTION AIR IS MIXING WITH AIR RETURN. THIS INSPECTOR SHUT OFF GAS, DISCONNECTED UNIT AND INFORMED OWNERS THAT THIS WAS AN EXTREMELY DANGEROUS CONDITION AND THAT UNIT WAS NOT TO BE USED.

12) RESTROOMS HAVE BEEN GREATLY MODIFIED WITHOUT PERMITS. WATER CLOSETS HAVE BEEN ADDED, WATER CLOSETS HAVE BEEN RELOCATED, LAVATORIES HAVE BEEN RELOCATED, SHOWERS AND BATHS HAVE BEEN REMOVED; ALL THIS WORK WAS DONE WITHOUT PERMITS AND IS IN VIOLATION OF THE PLUMBING CODES. DUE TO READILY APPARENT VIOLATIONS OF MATERIAL TYPES, AND INSTALLATION PROBLEMS IT WILL BE NECESSARY TO UNCOVER ALL UNDERGROUND WORK FOR INSPECTION. MUCH OF THIS ILLEGAL WORK IS CONNECTED TO THE PREVIOUSLY MENTIONED VIOLATION #4.

13) THE EGRESS PATHS AND MAIN CORRIDOR HAS BEEN MODIFIED IN THIS BUILDING WITHOUT PERMITS.

14) THE REAR DOOR EXITS TO A LOCKED YARD. EGRESS TO THE PUBLIC WAY MUST BE PROVIDED.