Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T10ME00626
Permit Details
Apply Date:
10/20/2010
Applicant:
BHATT CLYDA J
Description:
REPLACE ROOF MOUNTED A/C UNIT
Contractors:
- AMERICAN HOME MAINTENANCE INC *APA*
Permit Reviews
Permit Number - T10ME00626
Permit Status: Final
Permit Description: REPLACE ROOF MOUNTED A/C UNIT
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
10/20/2010 | MECHANICAL | 10/20/2010 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T10ME00626
Permit Status: Final
Permit Description: REPLACE ROOF MOUNTED A/C UNIT
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
10/20/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T10ME00626
Permit Description: REPLACE ROOF MOUNTED A/C UNIT
Total Completed Inspections - 3
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/21/2010 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1) BLOCK AND CLAMP GAS LINE ON ROOF 2) PROVIDE PROTECTION FROM SUN DAMAGE FOR CANVAS CONNECTORS 3) PROVIDE MINIMUM 1/8" PER FT. SLOPE ON CONDENSATE DRAIN AND SECURE PVC TO BLOCKS 4) RELOCATE ELECTRIC CONDUIT BLOCKING SERVICE ACCESS PANEL |
10/21/2010 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* |
04/05/2011 | PERMIT FINALED | JWEATHER | Approved |