Permit: T10ME00078
Permit Details
Apply Date:
02/10/2010
Applicant:
BRIAN FISHER
Description:
HOOD INSPECTION
Outstanding Activity Conditions
Permit Number - T10ME00078
Permit Status: Expired
Permit Description: HOOD INSPECTION
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 02/10/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T10ME00078
Permite Description: HOOD INSPECTION
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/11/2010 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : THE HOOD & GREASE DUCTS UP TO THE ROOF ARE APPROVED TYPE I. HOWEVER, THE EXHAUST FANS & DUCTS ON THE ROOF ARE NOT TYPE I. PROVIDE AN ENGINEERED DRAWING TO PROPERLY SIZE NEW FANS & DUCTS. MAKE UP AIR MUST BE INTERLOCKED WITH EXHAUST FAN. |