Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Apply Date:
02/09/2010
Applicant:
QUINN KRISTI
Description:
replace exsisting split system with new split system
Contractors:
  • RUSSETT SERVICE CORPORATION, *C

Outstanding Activity Conditions

Permit Number - T10ME00076
Permit Status: Expired
Permit Description: replace exsisting split system with new split system
Total Outstanding Activity Conditions - 1
Date Name
02/09/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T10ME00076
Permite Description: replace exsisting split system with new split system
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
MECHANICAL - FINAL N/A Not Inspected

Documents

File Name Document Type  
None DOCUMENTS VIEW