Permit: T10ME00045
Permit Details
Apply Date:
01/27/2010
Applicant:
LIBBY WRIGHT
Description:
COURTESY MECHANICAL HOOD SYSTEM INSPECTION
Outstanding Activity Conditions
Permit Number - T10ME00045
Permit Status: Expired
Permit Description: COURTESY MECHANICAL HOOD SYSTEM INSPECTION
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
01/27/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T10ME00045
Permite Description: COURTESY MECHANICAL HOOD SYSTEM INSPECTION
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/02/2010 | BUILDING - PROGRESS | N/A | Partial Approval | 1) FAN ON ROOF NON-COMPLIANT FOR TYPE 1 HOOD. MUST BE REPLACED (BLOWER AND DUCT TO BLOWER). 2) ANSUL SYSTEM MUST BE UPDATED TO MEET UL-300 3) STOVE OK, OTHER KITCHEN EQUIPMENT OK, PLUMBING APPEARS OK. 4) PROPERTY LINE WALL NEEDS TO BE 2 HOUR RATED 5) MECHANICAL REPAIRS MAY BE DONE ON THIS ACTIVITY IF CONTRACTOR BRINGS PLANS AND PAYS CORRECT FEES. A CERTIFICATE OF OCCUPANCY WILL STILL BE REQUIRED AND THAT SHALL BE UNDER SEPARATE PERMIT. |
02/02/2010 | MECHANICAL - FINAL | N/A | Denied |