Permit Details

Status:
Final
Type:
SINGLE FAMILY OTHER
Address NEW:
1137 S DUQUESNE DR
Apply Date:
11/12/2010
Applicant:
ANDY FITZPATRICK
Description:
REAL ESTATE RECONNECT FOR TESTING; ANDY FITZPATRICK; 886-7334

Outstanding Activity Conditions

Permit Number - T10EL02590
Permit Status: Final
Permit Description: REAL ESTATE RECONNECT FOR TESTING; ANDY FITZPATRICK; 886-7334
Total Outstanding Activity Conditions - 1
Date Name
11/12/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T10EL02590
Permit Description: REAL ESTATE RECONNECT FOR TESTING; ANDY FITZPATRICK; 886-7334
Total Completed Inspections - 4
Date Description Inspector Results Comments
12/13/2010 ELECTRIC - FINAL RJIROUDE Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) KITCHEN COUNTERS, SINKS AND COOKING EQUIPMENT HAVE BEEN REMOVED, NEED WORKING KITCHEN TO MEET MINIMUM HABITABILITY REQUIREMENTS
2) RECEPT HANGING AT OPEN WALL-KITCHEN
3) KITCHEN COUNTER RECEPTS TO BE GFI PROTECTED
4) MISSING WALL PLATES
5) RECEPT BOXES LOOSE AND HANGING OUT OF WALLS
6) CEILING FANS NOT WIRED TO CODE
7) BATHROOM RECEPTS TO BE GFI PROTECTED
8) INSTALL SMOKE DETECTORS IN BEDROOMS. CHECK OPERATION OF EXISTING SMOKE DETECTORS
9) HAVE GROUNDING TYPE RECEPTS ON UNGROUNDED ELECTRICAL SYSTEM
10) OBTAIN SERVICES OF A QUALIFIED ELECTRICAL CONTRACTOR TO MAKE CORRECTIONS AND GO THROUGH ENTIRE ELECTRICAL SYSTEM
11) HAZARDOUS, NO RECONNECT ALLOWED
12/13/2010 ELECTRIC - RECONNECT RJIROUDE Approved IVRS - Inspection :
See detailed listing on site.| 999*
04/20/2011 TEP CLEARANCE - AM JWEATHER Approved RECN CLEARED PER R. MORENO
04/20/2011 PERMIT FINALED JWEATHER Approved