Permit: T10EL01382
Permit Details
Apply Date:
06/08/2010
Applicant:
DANIEL BADILLA
Description:
REPLACE:SERVICE PANEL 100AMP
Permit Reviews
Permit Number - T10EL01382
Permit Status: Expired
Permit Description: REPLACE:SERVICE PANEL 100AMP
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 06/08/2010 | ELECTRICAL | 06/08/2010 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T10EL01382
Permit Status: Expired
Permit Description: REPLACE:SERVICE PANEL 100AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/08/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T10EL01382
Permite Description: REPLACE:SERVICE PANEL 100AMP
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/11/2010 | ELECTRIC - SERVICE UPGRADE | N/A | Partial Approval | IVRS - Inspection :* |
| 06/11/2010 | ELECTRIC - FINAL | N/A | Partial Approval | IVRS - Inspection :* 1) 2ND UNIT IN BACK NEEDS TO BE PERMITTED 2) GROUNDING ELECTRODE SYSTEM REQUIRED ON UNIT IN BACK PER 250.32 NEC 3) TRI-PLEX TO LOW, 12' MINIMUM ABOVE F.G. 4) WIRING AT UNIT B USAFE CONNECTION 5) CONTRACTOR TO BRING WIRING UP TO CODE TO SUB-PANEL AT UNIT B |
Completed Inspections
Permit Status: Expired
Permit Number: T10EL01382
Permit Description: REPLACE:SERVICE PANEL 100AMP
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2010 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED FOR |