Permit: T10CM02575
Permit Details
Apply Date:
09/15/2010
Applicant:
N/A
Description:
REPLACE ROOFTOP AC UNIT; T10DV05566
Contractors:
- TRUSTED HEATING AND COOLING
Permit Reviews
Permit Number - T10CM02575
Permit Status: Final
Permit Description: REPLACE ROOFTOP AC UNIT; T10DV05566
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 09/15/2010 | OTHER | 09/15/2010 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T10CM02575
Permit Status: Final
Permit Description: REPLACE ROOFTOP AC UNIT; T10DV05566
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/15/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T10CM02575
Permit Description: REPLACE ROOFTOP AC UNIT; T10DV05566
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/07/2010 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1) TERMINATE CONDENSATE TO WITHIN 6" OF THE GROUND WITH AND ELBOW AND NIPPLE. PAINT WITH LATEX PAINT 2) PROVIDE REDWOOD OR PRESSURE TREATED 2 X 4 BLOCKING UNDER ELECTRIC CONDUITS AND CONDENSATE DRAIN 3) PROVIDE A SEDIMENT TRAP IN GAS LINE AT FURNACE CONNECTION 4) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON THE ROOF 5) PROVIDE MINIMUM 2" DUCT LINER IN EXPOSED DUCT ON THE ROOF. SEAL ALL JOINTS, SPOT WELDS AND CONNECTIONS |
| 03/10/2011 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* |
| 03/29/2011 | PERMIT FINALED | JWEATHER | Approved |