Permit: T10CM02508
Permit Details
Apply Date:
09/08/2010
Applicant:
N/A
Description:
ADDITION:SOLAR PHOTO VOLTAIC
Contractors:
- WESTCAP ENERGY INC
Permit Reviews
Permit Number - T10CM02508
Permit Status: Final
Permit Description: ADDITION:SOLAR PHOTO VOLTAIC
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
09/08/2010 | PLANS OK TO SUBMIT - RES | 11/10/2010 | COMPLETED |
11/10/2010 | RESIDENTIAL - BLDG/WWM | 11/16/2010 | COMPLETED |
11/17/2010 | RESUBMITTAL | 11/30/2010 | COMPLETED |
11/30/2010 | RESUBMITTAL | 11/30/2010 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T10CM02508
Permit Status: Final
Permit Description: ADDITION:SOLAR PHOTO VOLTAIC
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
09/08/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T10CM02508
Permit Description: ADDITION:SOLAR PHOTO VOLTAIC
Total Completed Inspections - 4
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/29/2010 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1) MAINTAIN WORKING CLEARANCES AT ELECTRICAL EQUIPMENT 110.26 2) LABELING TO BE PER 690.17 3) TIGHTEN LOOSE FITTINGS 4) OPEN INVERTER FOR INSPECTION 5) PLEASE VERIFY CONDUIT DEPTS PER 300.5 6) INSTALL WEEB LUG PER MANUFACTURERS INSTRUCTIONS 7) SUPPORT CONDUCTORS UP UNDER MODULES FOR PHYSICAL PROTECTION 8) ONLY ONE CONDUCTOR PER LUG TERMINATION |
12/29/2010 | BUILDING - FINAL | RHOLLAND | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
01/06/2011 | PERMIT FINALED | JWEATHER | Approved | |
01/06/2011 | TEP CLEARANCE - AM | JWEATHER | Approved | ECO CLEARED FOR "PHOTOVOLTAIC SYSTEM" PER R. HOLLANDER |