Permit Reviews

Permit Number - T10CM01310
Permit Status: Expired
Permit Description: NEW 1TON MINI SPLIT SYSTEM
Start Date Submittal Complete Date Status  
05/13/2010 OTHER 05/13/2010 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T10CM01310
Permit Status: Expired
Permit Description: NEW 1TON MINI SPLIT SYSTEM
Total Outstanding Activity Conditions - 1
Date Name
05/13/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T10CM01310
Permite Description: NEW 1TON MINI SPLIT SYSTEM
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
05/14/2010 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OK TO ELIMINATE LOWER COMBSUTION AIR OPENING AND USE THE ONE OPENING METHOD ALLOWED BY CODE FOR WATER HEATER
2) UPPER OPENING MUST BE MIN. 1 SQ. INCH PER 3,000 BTU
3) TERMINATE CONDENSATE TO WITHIN 6" OF THE GROUND WITH AN ELBOW AND NIPPLE
4) PROVIDE A PERMIT FOR NEW FURNACE AND CONDENSOR
5) NEEDS AN OVERFLOW SENSOR
6) CONDENSOR OVERFUSED
05/14/2010 MECHANICAL - FINAL N/A Denied IVRS - Inspection :