Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T10CM01015
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
2120 S CAMPBELL AV
Address NEW:
2120 S CAMPBELL AV
Apply Date:
04/14/2010
Applicant:
N/A
Description:
INSTALL:PACKAGE UNIT ON ROOF TOP
Contractors:
- APPLE PLUMBING AND COOLING LLC *
Permit Reviews
Permit Number - T10CM01015
Permit Status: Expired
Permit Description: INSTALL:PACKAGE UNIT ON ROOF TOP
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/14/2010 | OTHER | 04/14/2010 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T10CM01015
Permit Status: Expired
Permit Description: INSTALL:PACKAGE UNIT ON ROOF TOP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 04/14/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T10CM01015
Permite Description: INSTALL:PACKAGE UNIT ON ROOF TOP
Total Outstanding Inspections - 4
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2010 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE SEPERATE CIRCUIT FOR SERVICE OUTLET 2) UNIT NOT PROPERLY WIRED 3) PROVIDE BUSHING BETWEEN DISCONNECT AND UNIT 4) JOINTS ON ELBOW NOT PROPERLY SEALED, SEAL BOTTOM OF ALL DUCT 5) PROVIDE APPROVED STRAPS FOR ELECTRICAL CONDUIT 6) PROVIDE ISOMETRIC GAS PIPING DRAWINGS APPROVED BY CITY OF TUCSON 7) PROVIDE APPROVED ROOF LOAD CALC. APPROVED BY CITY OF TUCSON 8) PVC TO BE SUPPORTED UP OFF ROOF MIN. 1 1/2" 9) GAS PIPING SIZE CANNOT BE REDUCED AND THEN ENLARGED, TO ACCOMMODATE FITTINGS |
| 04/21/2010 | PLUMBING - GAS PRESSURE TEST | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
| 04/21/2010 | PLUMBING - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
| 04/21/2010 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |