Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
6225 E SPEEDWAY BL
Apply Date:
03/19/2010
Applicant:
N/A
Description:
REPLACE; EXHAUST HOOD W/SUPPORTING WALLS, REPLACE GAS LINE
Architects:
  • FIELDS, JAMES SLOAN
Contractors:
  • ARIZONA RESTAURANT SUPPLY INC

Permit Reviews

Permit Number - T10CM00685
Permit Status: Expired
Permit Description: REPLACE; EXHAUST HOOD W/SUPPORTING WALLS, REPLACE GAS LINE
Start Date Submittal Complete Date Status  
03/19/2010 COMMERCIAL-BLDG/FIRE/ZONING/ENG 03/19/2010 ACTIVE Review Details

Outstanding Activity Conditions

Permit Number - T10CM00685
Permit Status: Expired
Permit Description: REPLACE; EXHAUST HOOD W/SUPPORTING WALLS, REPLACE GAS LINE
Total Outstanding Activity Conditions - 1
Date Name
03/19/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T10CM00685
Permite Description: REPLACE; EXHAUST HOOD W/SUPPORTING WALLS, REPLACE GAS LINE
Total Outstanding Inspections - 4
Last Inspection Date Description Inspector Results Comments
FIRE - KITCHEN EXH HOOD FINAL N/A Not Inspected
05/07/2010 BUILDING - FINAL N/A Not ready for Inspection IVRS - Inspection :*
1) NEED FIRE C OF O
05/07/2010 PLUMBING - FINAL N/A Partial Approval IVRS - Inspection :*
1) ONLY LISTED GAS APPLIANCES/EQUIPMENT MAYBE USED
2) SOAP TEST ALL CONNECTIONS
3) OK TO CONNECT LISTED APPLIANCES AND DEMO ABANDON PIPING
4) RECALL FOR FINAL APPROVAL
05/07/2010 MECHANICAL - FINAL N/A Partial Approval IVRS - Inspection :*
1) NEED HEAT SENSOR TEST
2) EVERYTHING ELSE IS OK

Completed Inspections

Permit Status: Expired
Permit Number: T10CM00685
Permit Description: REPLACE; EXHAUST HOOD W/SUPPORTING WALLS, REPLACE GAS LINE
Total Completed Inspections - 7
Date Description Inspector Results Comments
04/08/2010 FRAMING GDABBS Approved IVRS - Inspection :*
04/09/2010 SHEET ROCK NAILING GDABBS Approved IVRS - Inspection :*
04/09/2010 PLUMBING - GAS PRESSURE TEST BBENEDON Approved IVRS - Inspection :*
04/09/2010 PLUMBING - INTERMEDIATE BBENEDON Approved IVRS - Inspection :*
04/23/2010 MECHANICAL - HOODS JMILITEL Approved IVRS - Inspection :*
04/23/2010 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
04/23/2010 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
1) CHECKED WELDS ON GREASE DUCTS
2) WILL CHECK REMAINDER OF FIRE WRAP ON FINAL