Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address:
1219 S 6TH AV
Address NEW:
1219 S 6TH AV
Apply Date:
05/12/2010
Applicant:
UNITED FIRE EQUIPMENT CO.
Description:
KITCHEN EXHAUST HOOD FIRE SYSTEM
Contractors:
  • UNITED FIRE EQUIPMENT CO.

Permit Reviews

Permit Number - T10BU00777
Permit Status: Expired
Permit Description: KITCHEN EXHAUST HOOD FIRE SYSTEM
Start Date Submittal Complete Date Status  
05/12/2010 MECHANICAL 05/12/2010 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T10BU00777
Permit Status: Expired
Permit Description: KITCHEN EXHAUST HOOD FIRE SYSTEM
Total Outstanding Activity Conditions - 1
Date Name
05/12/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T10BU00777
Permite Description: KITCHEN EXHAUST HOOD FIRE SYSTEM
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
10/27/2010 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HOOD AND EXHAUST SYSTEM ARE NOT TYPE 1
2) PROVIDE ENGINEERED TYPE 1 DUCT AND EXHAUST
3) PROVIDE MINIMUM HOOD SIZE FOR EXISTING EQUIPMENT
12/21/2010 FIRE - KITCHEN EXH HOOD FINAL N/A Cancelled IVRS - RI canceled

Documents

File Name Document Type  
None DOCUMENTS VIEW
001_HOOD.TIF FIRE PLANS VIEW