Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Apply Date:
05/12/2010
Applicant:
S S C SECURITY SYSTEMS ,
Description:
FIRE ALARM
Contractors:
  • S S C SECURITY SYSTEMS ,

Outstanding Activity Conditions

Permit Number - T10BU00770
Permit Status: Expired
Permit Description: FIRE ALARM
Total Outstanding Activity Conditions - 1
Date Name
05/12/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T10BU00770
Permite Description: FIRE ALARM
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
07/07/2010 FIRE - ALARM FINAL N/A Partial Approval Partial approval 7/7/10
1.) All appliances tested and approved
2.) All signals transmitted properly to central alarm
3.) Need mechanical final approval
a.) problem with the "duct detectors" shutting off

Documents

File Name Document Type  
001_ALARM.TIF FIRE PLANS VIEW
002_ALARM.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW