Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address:
6635 E GRANT RD
Apply Date:
01/26/2010
Applicant:
METRO FIRE EQUIPMENT INC
Description:
FIRE SUPPRESSION SYTSTEM
Contractors:
  • METRO FIRE EQUIPMENT INC

Permit Reviews

Permit Number - T10BU00141
Permit Status: Final
Permit Description: FIRE SUPPRESSION SYTSTEM
Start Date Submittal Complete Date Status  
01/26/2010 MECHANICAL 01/26/2010 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T10BU00141
Permit Status: Final
Permit Description: FIRE SUPPRESSION SYTSTEM
Total Outstanding Activity Conditions - 1
Date Name
01/26/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T10BU00141
Permit Description: FIRE SUPPRESSION SYTSTEM
Total Completed Inspections - 4
Date Description Inspector Results Comments
03/10/2010 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
2) OK FOR FIRE FIANL
03/10/2010 FIRE - KITCHEN EXH HOOD FINAL DSIWARSKI Approved
03/10/2010 FIRE - KITCHEN EXH HOOD FINAL DSIWARSKI Approved Make up air did not shut off when system was activated and the exhaust fan shut off.
03/11/2010 PERMIT FINALED JWEATHER Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW
001_FIRE SUPP SYSTEM.TIF FIRE PLANS VIEW