Permit: T09OT01821
Permit Details
Apply Date:
08/28/2009
Applicant:
JUAN E ASON
Description:
C OF O:RESTAURANT 7 MARES
Permit Reviews
Permit Number - T09OT01821
Permit Status: Expired
Permit Description: C OF O:RESTAURANT 7 MARES
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 08/28/2009 | C OF O | 09/02/2009 | COMPLETED |
| 09/15/2009 | C OF O | 09/15/2009 | ACTIVE |
Outstanding Inspections
Permit Status: Expired
Permit Number: T09OT01821
Permite Description: C OF O:RESTAURANT 7 MARES
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2009 | CERTIFICATE OF OCCUPANCY | N/A | Not ready for Inspection | IVRS - Inspection :* 1. NEED FIRE C OF O 2. REPAIR ROOF LEAK ABOVE KITCHEN 3. REMOVE TRASH FROM REAR EXTERIOR 4. INSTALL ANTI ? VALVE ON EXT HOSE BIBS 5. INSTALL COVERS ON EXTERIOR CLEAN OUTS |
| 09/09/2009 | FIRE - FINAL | N/A | Denied | 1.) Need exit signs for both required exit doors. Signs must be illuminated. 2.) Need emergency back-up lights for both required exit doors. 3.) Provide a thumb-turn lock for the maine exit door or a keyed lock with a sign over the main door reading,"DOOR MUST REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED". 4.) Need panic hardware for secondary exits. 5.) Rear exit doors must swing in direction of travel. 6.) The screen security doors on the rear exits must be removed. 7.) Rear exit discharge must lead to a public way. The path must be unobstructed at all times and the gate must be readily openible without the use of a key. 8.) Place a directional exit sign out side both rear doors directing to public way. 9.) Hood exhaust system needs to be inspected and serviced. |