Permit Details

Status:
Closed
Type:
COMMERCIAL OTHER
Address NEW:
2575 N CAMPBELL AV
Apply Date:
06/09/2009
Applicant:
RAFAEL D GARCIA
Description:
C OF O: BAKERY

Permit Reviews

Permit Number - T09OT01172
Permit Status: Closed
Permit Description: C OF O: BAKERY
Start Date Submittal Complete Date Status  
06/09/2009 C OF O 06/10/2009 COMPLETED Review Details
06/18/2009 C OF O 06/18/2009 COMPLETED Review Details

Outstanding Inspections

Permit Status: Closed
Permit Number: T09OT01172
Permite Description: C OF O: BAKERY
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
HEALTH DEPT - FINAL 724-7908 N/A Not Inspected
06/30/2009 CERTIFICATE OF OCCUPANCY N/A Not ready for Inspection IVRS - Inspection :*
1) BASELINE DEPICITIONS ARE CORRECT AS SUBMITTED

Completed Inspections

Permit Status: Closed
Permit Number: T09OT01172
Permit Description: C OF O: BAKERY
Total Completed Inspections - 1
Date Description Inspector Results Comments
06/11/2009 FIRE - FINAL DRAMIREZ Approved 1.) Need updated and approved floor plans.
2.) Current occupancy load requires 2 exits for this property. The customer area does not indicate room for 120 occupants.
3.) Panic hardware and illuninated exiting will be required unless occupancy load can be lowered below 50 occupants.
4.) Repair or replace broken glass on north exit door.
5.) Cover plates x 3.
6.) Extension cords for temporary use only not as substitutes for permanent wiring.
7.) Slide-bolts are prohibited. Remove from rear door.
8.) Repair the interior release mechanisim for the exterior cooler.

Documents

File Name Document Type  
None DOCUMENTS VIEW