Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address:
1915 E 36TH ST
Address NEW:
1915 E 36TH ST
Apply Date:
04/01/2009
Applicant:
TUCSON YOUTH DEVELOPMENT SCHOOL
Description:
C OF O: YOUTH DEVELOPMENT SCHOOL (YOUTHWORKS)

Permit Reviews

Permit Number - T09OT00640
Permit Status: Expired
Permit Description: C OF O: YOUTH DEVELOPMENT SCHOOL (YOUTHWORKS)
Start Date Submittal Complete Date Status  
04/01/2009 C OF O 04/01/2009 COMPLETED Review Details

Outstanding Inspections

Permit Status: Expired
Permit Number: T09OT00640
Permite Description: C OF O: YOUTH DEVELOPMENT SCHOOL (YOUTHWORKS)
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
04/02/2009 CERTIFICATE OF OCCUPANCY N/A Not ready for Inspection IVRS - Inspection :*
1. NEED FIRE C OF O
2. PLUG HOLES IN CIRCUIT BREAKER PANEL AND LABEL CIRCUITS
3. WIRING FOR OVERHEAD LIGHTS NEEDS TO BE DONE CORRECTLY
4. ANTI-SIPHON VALVES ON EXT. HOSE BIBS
5. APPROVED PLAN DOES NOT MATCH EXISTING
NO ACCESSIBLE BATHROOM AND NEW WALL
6. RATED CORRIDOR MISSING RATED DOOR LABELS
04/02/2009 FIRE - FINAL N/A Denied 1.) Current plans are for a "B" occupancy and plans do not match the buildings foot print. The occupancy is being changed to an "E" occupany. Need to submit new plans reflecting the change and they must be drawn by an architect.
2.) "E" occupancies require sprinklers or a door the exits directly from the classroom directly to the exterior of the building and to a public way or a minimum distance of 50 ft. from the building.
3.) Buildings having a minimum of 20 sprinkler heads require a fire alarm system to monitor a water flow and tamper alarm.
4.) Main and rear exit signs needs repair.
5.) Remove the thumb-turn lock from the front and rear exit doors. Only one locking device is allowed.
6.) Emergency back-up lighting for the front and the rear exits is required.
7.) Portable extinguishers need annual inspection. They need to be mounted, labled and readily accessable or they can be removed.
8.) Cover all open wiring.
9.) Replace cover plates.
10.) Need panic hardware on rear exits.
11.) Roof sheeting for the ramada outside needs replacing.