Permit: T09OT00477
Permit Details
Apply Date:
03/06/2009
Applicant:
WILLIAM RODRIGUES SR
Description:
C OF O: RETAIL
Permit Reviews
Permit Number - T09OT00477
Permit Status: Expired
Permit Description: C OF O: RETAIL
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
03/06/2009 | C OF O | 03/06/2009 | COMPLETED |
Outstanding Inspections
Permit Status: Expired
Permit Number: T09OT00477
Permite Description: C OF O: RETAIL
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/10/2009 | CERTIFICATE OF OCCUPANCY | N/A | Not ready for Inspection | IVRS - Inspection :* OWNER CANCELED |
04/10/2009 | FIRE - FINAL | N/A | Denied | 1.) Repair burnt out exit signs or remove from service.(Not required) 2.) Repair burnt out emergency back-up lighting or remove from service.(Not required) 3.) Reverse the locking position of the locking device on the door between the back room and the main floor. 4.) Only one lock is permitted per door. The rear door has a thumb-turn lock and panic hardware. Remove one or the other. |