Permit: T09ME00798
Permit Details
Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
741 S SHERWOOD VILLAGE DR
Address NEW:
741 S SHERWOOD VILLAGE DR
Apply Date:
12/15/2009
Applicant:
TEMP CON INC *C
Description:
REPLACE: ROOF MOUNTED 4 TON GAS PACK (APA)
Contractors:
- TEMP CON INC *C
Outstanding Activity Conditions
Permit Number - T09ME00798
Permit Status: Final
Permit Description: REPLACE: ROOF MOUNTED 4 TON GAS PACK (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/15/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T09ME00798
Permit Description: REPLACE: ROOF MOUNTED 4 TON GAS PACK (APA)
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2009 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1) INSULATE EXPOSED METAL DUCT IN FURNACE CLOSET 2) PROVIDE THE REQUIRED DRAWING TO ALLOW NEW ROOF TOP EQUIPMENT 3) 3/8" X 18" GAS FLEX NOT ADEQUATE FOR 100,000 BTU 4) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF WITH A BUBBLE TYPE COVER 5) PROVIDE A CHASE NIPPLE IN ELECTRIC DISCONNECT |
| 01/08/2010 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | |
| 01/12/2010 | PERMIT FINALED | JWEATHER | Approved |