Permit: T09ME00740
Permit Details
Apply Date:
11/18/2009
Applicant:
AMERICAN HOME MAINTENANCE INC *C
Description:
REPLACE: 3 TON GAS SPLIT SYSTEM (APA)
Contractors:
- AMERICAN HOME MAINTENANCE INC *C
Outstanding Activity Conditions
Permit Number - T09ME00740
Permit Status: Expired
Permit Description: REPLACE: 3 TON GAS SPLIT SYSTEM (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 11/18/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T09ME00740
Permite Description: REPLACE: 3 TON GAS SPLIT SYSTEM (APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2010 | MECHANICAL - FINAL | N/A | Partial Approval | IVRS - Inspection :* 1) PROVIDE THE REQUIRED GFI SERVICE RECEPT AT THE CONDENSOR 2) SEAL THE HOLE WHERE THE REFIDGERATION LINE SET EXITS UNDER THE EAVE 3) EXTEND DBL WALL VENT PIPE MINIMUM 3' ABOVE THE COMBUSTION AIR INTAKE WITH AN APPROVED VENT CAP |