Permit: T09ME00593
Permit Details
Apply Date:
09/09/2009
Applicant:
QUINN KRISTI
Description:
REMOVE AND REPLACE EXSISTING HEATING AND COOLING SYSTEM WITH 5 TON SPLIT GAS/ELECTRIC SYSTEM
Contractors:
- RUSSETT SERVICE CORPORATION, *C
Outstanding Activity Conditions
Permit Number - T09ME00593
Permit Status: Expired
Permit Description: REMOVE AND REPLACE EXSISTING
HEATING AND COOLING SYSTEM
WITH 5 TON SPLIT GAS/ELECTRIC
SYSTEM
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/09/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T09ME00593
Permite Description: REMOVE AND REPLACE EXSISTING
HEATING AND COOLING SYSTEM
WITH 5 TON SPLIT GAS/ELECTRIC
SYSTEM
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2009 | MECHANICAL - FINAL | N/A | Denied | SECURE THE DISCONNECT AND ELECTRIC CONDUITS ON THE ROOF. PROVIDE THE REQUIRED GFI SERVICESRECEPTACLE ON THE ROOF. THE GAS FLEX CONNECTION IS NOT ADEQUATE FOR 90,000 BTU FURNACE. PROVIDE INSTALL INSTRUCTIONS FOR EVAP COIL AND BUILD TRAP PER MANUFACTURERS INSTRUCTIONS. PROVIDE THE LISTING FOR THE TRAP THAT WAS USED. TRAP MAY NOT BE APPROVED. PROVIDE A PERMIT FOR NEW SOLAR WATER HEATER SYSTEM AND SCHEDULE INSPECTION. ALL SOLAR COLLECTORS MUST BE LISTED. |