Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T09ME00538
Permit Details
Apply Date:
08/25/2009
Applicant:
HARRIS KEVIN
Description:
Replace existing 2 ton package unit with a new 2 ton package unit.
Contractors:
- HARRIS BUILDING AND DEVELOPMENT INC
Outstanding Activity Conditions
Permit Number - T09ME00538
Permit Status: Expired
Permit Description: Replace existing 2 ton package unit with a new 2 ton package unit.
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
08/25/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T09ME00538
Permite Description: Replace existing 2 ton package unit with a new 2 ton package unit.
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/25/2009 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A TRAP ON CONDENSATE DRAINS 2) TERMINATE INTO AN APPROVED LOCATION 3) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLU 4) SLOPE ALL SECTIONS OF CONDENSATE PIPE MINIMUM 1/8" PER FT. 5) STEP UP TO 1" AFTER 1ST TEE 6) PROVIDE FRESH AIR INTAKE ON A/C UNITS 7) SUPPORT ELECTRIC DISCONNECTS 8) USE PROPER ELECTRIC FITTING AT LOW VOLTAGE CONDUIT 9) VENTS ON CONDENSATE TRAPS MUST BE DOWNSTREAM OF THE TRAP 10) PROVIDE PERMITS FOR 5029 & 5033 11) SAME NOTES FOR 4911, DO NOT MOUNT DISCONNECT TO SERVICE PANEL-UNIT OVER FUSED |