Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
831 N CAMINO MIRAMONTE
Apply Date:
07/21/2009
Applicant:
TRAVIS FRENCH
Description:
REPLACE: ELECTRIC PANEL AND METER

Permit Reviews

Permit Number - T09EL01692
Permit Status: Expired
Permit Description: REPLACE: ELECTRIC PANEL AND METER
Start Date Submittal Complete Date Status  
07/21/2009 ELECTRICAL 07/21/2009 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T09EL01692
Permit Status: Expired
Permit Description: REPLACE: ELECTRIC PANEL AND METER
Total Outstanding Activity Conditions - 1
Date Name
07/21/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T09EL01692
Permite Description: REPLACE: ELECTRIC PANEL AND METER
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
08/25/2009 ELECTRIC - SERVICE UPGRADE N/A Partial Approval IVRS - Inspection :*
1) INSTALL GROUNDING ELECTRODE SYSTEM PER 250.50,250.52 AND 250.64
2) NEED REJECTION PINS
3) NO LOAD FOR 3 PHASE CONNECTIONS
4) TIGHTEN CONNECTOR BACK OF ALL IN/OUT
5) NEED PERMANENT METAL ADDRESS LABEL
6) FINISH RISER STRAPPING-BOTH RISERS
7) STRAP GROUNDING CONDUCTORS TO STRUCTURE
8) CHECK LOAD CONNECTIONS FOR HOUSE PANEL NEXT INSPECTION BY 8/26/09
08/25/2009 ELECTRIC - FINAL N/A Partial Approval IVRS - Inspection :*

Completed Inspections

Permit Status: Expired
Permit Number: T09EL01692
Permit Description: REPLACE: ELECTRIC PANEL AND METER
Total Completed Inspections - 1
Date Description Inspector Results Comments
08/26/2009 TEP CLEARANCE - AM JWEATHER Approved INCR CLEARED PER R. HOLLANDER

Documents

File Name Document Type  
None DOCUMENTS VIEW