Permit: T09EL01692
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
831 N CAMINO MIRAMONTE
Address NEW:
831 N CAMINO MIRAMONTE
Apply Date:
07/21/2009
Applicant:
TRAVIS FRENCH
Description:
REPLACE: ELECTRIC PANEL AND METER
Permit Reviews
Permit Number - T09EL01692
Permit Status: Expired
Permit Description: REPLACE: ELECTRIC PANEL AND METER
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 07/21/2009 | ELECTRICAL | 07/21/2009 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T09EL01692
Permit Status: Expired
Permit Description: REPLACE: ELECTRIC PANEL AND METER
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 07/21/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T09EL01692
Permite Description: REPLACE: ELECTRIC PANEL AND METER
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2009 | ELECTRIC - SERVICE UPGRADE | N/A | Partial Approval | IVRS - Inspection :* 1) INSTALL GROUNDING ELECTRODE SYSTEM PER 250.50,250.52 AND 250.64 2) NEED REJECTION PINS 3) NO LOAD FOR 3 PHASE CONNECTIONS 4) TIGHTEN CONNECTOR BACK OF ALL IN/OUT 5) NEED PERMANENT METAL ADDRESS LABEL 6) FINISH RISER STRAPPING-BOTH RISERS 7) STRAP GROUNDING CONDUCTORS TO STRUCTURE 8) CHECK LOAD CONNECTIONS FOR HOUSE PANEL NEXT INSPECTION BY 8/26/09 |
| 08/25/2009 | ELECTRIC - FINAL | N/A | Partial Approval | IVRS - Inspection :* |
Completed Inspections
Permit Status: Expired
Permit Number: T09EL01692
Permit Description: REPLACE: ELECTRIC PANEL AND METER
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2009 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER R. HOLLANDER |