Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
7279 E FREESTONE DR
Apply Date:
07/06/2009
Applicant:
TADES INC
Description:
ELECTRIC:UPGRADE TO 200AMP
Contractors:
  • TADES INC

Permit Reviews

Permit Number - T09EL01585
Permit Status: Expired
Permit Description: ELECTRIC:UPGRADE TO 200AMP
Start Date Submittal Complete Date Status  
07/06/2009 ELECTRICAL 07/06/2009 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T09EL01585
Permit Status: Expired
Permit Description: ELECTRIC:UPGRADE TO 200AMP
Total Outstanding Activity Conditions - 1
Date Name
07/06/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T09EL01585
Permite Description: ELECTRIC:UPGRADE TO 200AMP
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
07/07/2009 ELECTRIC - SERVICE UPGRADE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/07/2009 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CLOSE OPEN BREAKER POSITIONS IN PANEL COVER
2) NEED PANEL DIRECTORY
3) BOND WATER AND GAS PIPING
4) EXPLAIN INSTALLED BAR AT BOTTOM OF PANEL, NOT PART OF MANUFACTURERS PANEL INSTALL
5) NEED 2 GROUND RODS MINIMUM 6' APART
6) EXPLAIN ALL NEW ROMEX CABLES INSTALLED INTO PANEL AND ALL NEW WORK NEEDS PLAND & PERMITS
7) SEAL OPENING IN BACK OF PANEL AT WIRE ENTRY WITH NON COMBUSTIBLE MATERIAL
8) BOND NIPPLE BETWEEN METER & PANEL AND BOND RISER
9) VERIFY PERMITS FOR NEW WATER HEATER AND ROOF TOP A/C UNIT
10) RECALL WHEN READY
11) SERVICE ENERGIZED WITHOUT APPROVAL
12) CALLED KATHY AT TEP NOT AWARE OF SERVICE UPGRADE AT THIS ADDRESS