Permit: T09EL00894
Permit Details
Status:
Closed
Type:
SINGLE FAMILY OTHER
Address:
202 E PENNSYLVANIA DR
Address NEW:
202 E PENNSYLVANIA DR
Apply Date:
04/23/2009
Applicant:
SAAVEDRA JOAQUIN A
Description:
RECONNECT:ELECTRIC:SFR
Outstanding Activity Conditions
Permit Number - T09EL00894
Permit Status: Closed
Permit Description: RECONNECT:ELECTRIC:SFR
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 04/23/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Closed
Permit Number: T09EL00894
Permite Description: RECONNECT:ELECTRIC:SFR
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2009 | ELECTRIC - RECONNECT | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE MINIMUM 2" RISER 2) INSTALL GROUND ROD SYSTEM 3) BOND GAS AND WATER 4) CHANGE OR PROVIDE UPGRADE PERMIT 5) SECURE #4 TO BLDG 6) PROVIDE SQUARE "D" BREAKERS TO MATCH PANEL 7) 15 AMP BREAKERS REQUIRED 14-2 WIRING 8) STORAGE ROOM ON PROPERTY LINE WILL BE TURNED INTO DNR 9) CONSULT TEP FOR POSSBLE NEW LOCATION OF SERVICE DROP 10) PROVIDE 12' CLEARANCE DROP OVER VEHICLES CONSULT WITH TEP 11) UNABLE TO OPEN MAIN DISCONNECT 12) UPGRADE REQUIRED 13) OVER 6 BREAKERS REQUIRE DISCONNECT |