Permit Details

Status:
Expired
Type:
COMMERCIAL ALTERATION
Address:
5550 E 1ST ST
Address NEW:
5550 E 1ST ST
Apply Date:
09/30/2009
Applicant:
N/A
Description:
TI:NEW KITCHEN EXHAUST HOOD
Contractors:
  • OLD PUEBLO REMODELERS ACC ,

Permit Reviews

Permit Number - T09CM02628
Permit Status: Expired
Permit Description: TI:NEW KITCHEN EXHAUST HOOD
Start Date Submittal Complete Date Status  
09/30/2009 COMMERCIAL TI 10/01/2009 COMPLETED Review Details
10/14/2009 REVISION - - 1ST 10/14/2009 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T09CM02628
Permit Status: Expired
Permit Description: TI:NEW KITCHEN EXHAUST HOOD
Total Outstanding Activity Conditions - 1
Date Name
09/30/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T09CM02628
Permite Description: TI:NEW KITCHEN EXHAUST HOOD
Total Outstanding Inspections - 8
Last Inspection Date Description Inspector Results Comments
BUILDING - FINAL N/A Not Inspected
ELECTRIC - INTERMEDIATE N/A Not Inspected
ELECTRIC - ABOVE CEILING N/A Not Inspected
MECHANICAL - HOODS N/A Not Inspected
FIRE SPKLR - FINAL N/A Not Inspected
FIRE - ALARM FINAL N/A Not Inspected
FIRE - KITCHEN EXH HOOD FINAL N/A Not Inspected
11/24/2009 MECHANICAL - FINAL N/A Partial Approval IVRS - Inspection :*
1) MAKE UP AIR NOT SUPPLYING REQUIRED AMOUNT
2) MAKE UP AIR DUCT NOT SIZED PER PLAN
3) EVAP COOLER REQUIRES A CLEAN MACHINE
4) PROVIDE A DRAIN ON EVAP COOLER
5) HEAT SENSOR NOT WORKING
6) CAPTURE AND CONTAINMENT TEST OK

Completed Inspections

Permit Status: Expired
Permit Number: T09CM02628
Permit Description: TI:NEW KITCHEN EXHAUST HOOD
Total Completed Inspections - 7
Date Description Inspector Results Comments
10/02/2009 FRAMING JBURGE Approved IVRS - Inspection :*
1) DETAILS #201, 203-OK TO HANG NEW STOVE HOOD
2) SHEETROCK OK
10/30/2009 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
10/30/2009 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
1) CHECKED 2 LAYERS OF FIRE WRAP
2) OK TO INSTALL GREASE DUCT
11/10/2009 PLUMBING - GAS PRESSURE TEST BBENEDON Approved IVRS - Inspection :*
11/10/2009 PLUMBING - GAS PRESS TEST FNL BBENEDON Approved IVRS - Inspection :*
11/12/2009 PLUMBING - FINAL BBENEDON Approved IVRS - Inspection :*
11/24/2009 ELECTRIC - FINAL RMORENO Approved IVRS - Inspection :*
1) ITEMS ON LIST OK

Documents

File Name Document Type  
001_CVR-K.TIF CONSTRPLANS VIEW
002_C1-K.TIF CONSTRPLANS VIEW
003_A1.0K.TIF CONSTRPLANS VIEW
004_A2.0K.TIF CONSTRPLANS VIEW
005_A3.0K.TIF CONSTRPLANS VIEW
006_S1.0.TIF CONSTRPLANS VIEW
007_M-1.TIF CONSTRPLANS VIEW
008_M-2.TIF CONSTRPLANS VIEW
009_E1.0.TIF CONSTRPLANS VIEW
001_P-1.TIF CONSTRPLANS VIEW
None DOCUMENTS VIEW