Permit: T09CM02628
Permit Details
Apply Date:
09/30/2009
Applicant:
N/A
Description:
TI:NEW KITCHEN EXHAUST HOOD
Contractors:
- OLD PUEBLO REMODELERS ACC ,
Permit Reviews
Permit Number - T09CM02628
Permit Status: Expired
Permit Description: TI:NEW KITCHEN EXHAUST HOOD
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 09/30/2009 | COMMERCIAL TI | 10/01/2009 | COMPLETED |
| 10/14/2009 | REVISION - - 1ST | 10/14/2009 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T09CM02628
Permit Status: Expired
Permit Description: TI:NEW KITCHEN EXHAUST HOOD
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/30/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T09CM02628
Permite Description: TI:NEW KITCHEN EXHAUST HOOD
Total Outstanding Inspections - 8
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| BUILDING - FINAL | N/A | Not Inspected | ||
| ELECTRIC - INTERMEDIATE | N/A | Not Inspected | ||
| ELECTRIC - ABOVE CEILING | N/A | Not Inspected | ||
| MECHANICAL - HOODS | N/A | Not Inspected | ||
| FIRE SPKLR - FINAL | N/A | Not Inspected | ||
| FIRE - ALARM FINAL | N/A | Not Inspected | ||
| FIRE - KITCHEN EXH HOOD FINAL | N/A | Not Inspected | ||
| 11/24/2009 | MECHANICAL - FINAL | N/A | Partial Approval | IVRS - Inspection :* 1) MAKE UP AIR NOT SUPPLYING REQUIRED AMOUNT 2) MAKE UP AIR DUCT NOT SIZED PER PLAN 3) EVAP COOLER REQUIRES A CLEAN MACHINE 4) PROVIDE A DRAIN ON EVAP COOLER 5) HEAT SENSOR NOT WORKING 6) CAPTURE AND CONTAINMENT TEST OK |
Completed Inspections
Permit Status: Expired
Permit Number: T09CM02628
Permit Description: TI:NEW KITCHEN EXHAUST HOOD
Total Completed Inspections - 7
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2009 | FRAMING | JBURGE | Approved | IVRS - Inspection :* 1) DETAILS #201, 203-OK TO HANG NEW STOVE HOOD 2) SHEETROCK OK |
| 10/30/2009 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* |
| 10/30/2009 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* 1) CHECKED 2 LAYERS OF FIRE WRAP 2) OK TO INSTALL GREASE DUCT |
| 11/10/2009 | PLUMBING - GAS PRESSURE TEST | BBENEDON | Approved | IVRS - Inspection :* |
| 11/10/2009 | PLUMBING - GAS PRESS TEST FNL | BBENEDON | Approved | IVRS - Inspection :* |
| 11/12/2009 | PLUMBING - FINAL | BBENEDON | Approved | IVRS - Inspection :* |
| 11/24/2009 | ELECTRIC - FINAL | RMORENO | Approved | IVRS - Inspection :* 1) ITEMS ON LIST OK |