Permit Details

Status:
Expired
Type:
COMMERCIAL ALTERATION
Apply Date:
01/21/2009
Applicant:
ROADRUNNER FIRE* C
Description:
2 HOODS- FIRE SUPPRESSION SYSTEMS
Contractors:
  • ROADRUNNER FIRE* C

Permit Reviews

Permit Number - T09BU00094
Permit Status: Expired
Permit Description: 2 HOODS- FIRE SUPPRESSION SYSTEMS
Start Date Submittal Complete Date Status  
01/21/2009 MECHANICAL 01/21/2009 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T09BU00094
Permit Status: Expired
Permit Description: 2 HOODS- FIRE SUPPRESSION SYSTEMS
Total Outstanding Activity Conditions - 1
Date Name
01/21/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T09BU00094
Permite Description: 2 HOODS- FIRE SUPPRESSION SYSTEMS
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
FIRE - KITCHEN EXH HOOD FINAL N/A Not Inspected
01/28/2009 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HOOD & GREASE DUCTS UP TO THE ROOF MEET TYPE I REQUIREMENTS
2. THE DUCT CONNECTING TO THE EXHAUST FANS DO NOT MEET TYPE I REQUIREMENTS
3. THE FAN FROM SMALL HOOD IS TYPE 1
4. THE FANS FROM LARGE HOOD DO NOT
MEET TYPE 1 REQUIREMENTS
5. MAKE UP AIR UNITS ARE NOT INTERLOCKED
6. PROVIDE PLANS & PERMITS FOR ANY MECHANICAL WORK