Permit: T08PL00640
Permit Details
Apply Date:
04/18/2008
Applicant:
ANNY HAHN
Description:
REPLACE: WATER HEATER (RESIDENCE)
Permit Reviews
Permit Number - T08PL00640
Permit Status: Expired
Permit Description: REPLACE: WATER HEATER (RESIDENCE)
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/18/2008 | PLUMBING | 04/18/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T08PL00640
Permit Status: Expired
Permit Description: REPLACE: WATER HEATER (RESIDENCE)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 04/18/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T08PL00640
Permite Description: REPLACE: WATER HEATER (RESIDENCE)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2008 | PLUMBING - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE SEDIMENT TRAP AT GAS ENTRY TO WATER HEATER 2. WATER HEATER VENT TO BE DOUBLE WALL LEAVING ENCLOSURE AND HAVE MINIMUM 1" CLEARANCE FROM COMBUSTIBLES 3. PROVIDE APPROVED FASTENERS AT ALL JOINTS OF VENT PIPING. NOTE: VENT TO TERMINATE 3' ABOVE COOLER INTAKE |