Permit: T08OT01384
Permit Details
Apply Date:
06/10/2008
Applicant:
RYAN GOMES
Description:
C OF O: RESTAURANT AND BAR
Permit Reviews
Permit Number - T08OT01384
Permit Status: Expired
Permit Description: C OF O: RESTAURANT AND BAR
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 06/10/2008 | C OF O | 06/10/2008 | COMPLETED |
Outstanding Inspections
Permit Status: Expired
Permit Number: T08OT01384
Permite Description: C OF O: RESTAURANT AND BAR
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| SIGN - FINAL | N/A | Not Inspected | ||
| 09/10/2008 | CERTIFICATE OF OCCUPANCY | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED LEVER HANDLES AT FRONT DOOR, RESTROOM DOORS AND RESTROOM SINKS 2. NEED ADA SIGNAGE AT RESTROOM 3. NEED 1" CLEARANCE AT WATER HEATER B-VENT THRU ROOF 4. CANNOT RUN ELEC. FROM EXHAUST FAN TO LIGHT AT RESTROOMS 5. NEED GRAB BARS IN RESTROOMS 6. NEED C OF O FIRE APPROVAL PRIOR TO THIS INSPECTION 7. NEED EXIT FROM REAR PATIO 8. CANNOT RUN EXTENSION CORD FOR PERMANENT WIRING |
| 09/10/2008 | FIRE - FINAL | N/A | Denied | 1. SECURE COMPRESSED CYLINDERS. 2. NEED ADDRESS NUMBERS ON FRONT OF BUILDING 15" HIGH. 3. REMOVE EXTENSION CORDS. 4. EXIT LIGHTS TO BE LIT & VISIBLE AT ALL TIMES. 5. PROVIDE EMERGENCY LIGHTS. 6. CANNOT RUN WIRES THROUGH WALLS. 7. REMOVE WROUGHT IRON HASPS OFF REAR EXIT. 8. REPAIR OR REMOVE REAR GATE. 9. USE ONLY APPROVED MULTIPLUG ADAPTERS. 10. HAVE A QUALIFIED ELECTRIAN PROPERLY INSTALL WIRING IN BATHROOMS FOR LIGHTS & IN AREAS WHERE EXTENSION CORDS NEED TO BE REMOVED. |