Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address NEW:
403 N 6TH AV #157
Apply Date:
12/02/2008
Applicant:
N B Y G ELECTRIC L L C
Description:
ELECTRIC:UPDATE
Contractors:
  • N B Y G ELECTRIC L L C

Permit Reviews

Permit Number - T08EL02228
Permit Status: Final
Permit Description: ELECTRIC:UPDATE
Start Date Submittal Complete Date Status  
12/02/2008 ELECTRICAL 12/09/2008 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T08EL02228
Permit Status: Final
Permit Description: ELECTRIC:UPDATE
Total Outstanding Activity Conditions - 1
Date Name
12/02/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T08EL02228
Permit Description: ELECTRIC:UPDATE
Total Completed Inspections - 8
Date Description Inspector Results Comments
03/19/2009 TEP CLEARANCE - PM BFLORES Approved INCR PER R.HOLLANDER
06/10/2009 ELECTRIC - OUTDOOR LIGHTING RHOLLAND Approved IVRS - Inspection :
See detailed listing on site.| 999*
06/10/2009 ELECTRIC - SERVICE UPGRADE RHOLLAND Approved IVRS - Inspection :
See detailed listing on site.| 999*
06/10/2009 ELECTRIC - CABLE DROP RHOLLAND Approved IVRS - Inspection :
See detailed listing on site.| 999*
06/10/2009 ELECTRIC - ABOVE CEILING RHOLLAND Approved IVRS - Inspection :
See detailed listing on site.| 999*
06/10/2009 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection :
See detailed listing on site.| 999*
06/10/2009 ELECTRIC - UNDERGROUND RHOLLAND Approved IVRS - Inspection :
See detailed listing on site.| 999*
11/03/2009 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) SUPPORT EXIT SIGN CONDUITS
2) SUPPORT CONDUITS AS PER CODES
3) FILL UNUSED OPENINGS IN BOXES
4) SUPPORT M/C CABLE TO TRAC LIGHTS
5) NEED TO VERIFY LOAD CALCULATIONS FOR TRAC LIGHTING
6) PLEASE PROVIDE ROOF ACCESS
7) DIMMERS OVER HEATING-VERIFY LOADS, CONDUCTOR FILL AND DERATING
8) PLEASE HAVE OLD WRITE UPS ON SITE