Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T08EL01557
Permit Details
Apply Date:
08/15/2008
Applicant:
JOHN MAC GREGOR
Description:
UPGRADE: ELECTRICAL FROM 100-200 AMP (RES) R1 ADD FEEDER & SUBPANEL IN LAUNDRY BUILDING
Permit Reviews
Permit Number - T08EL01557
Permit Status: Expired
Permit Description: UPGRADE: ELECTRICAL FROM 100-200 AMP (RES)
R1 ADD FEEDER & SUBPANEL IN LAUNDRY BUILDING
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/29/2008 | ELECTRICAL | 10/29/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T08EL01557
Permit Status: Expired
Permit Description: UPGRADE: ELECTRICAL FROM 100-200 AMP (RES)
R1 ADD FEEDER & SUBPANEL IN LAUNDRY BUILDING
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/15/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T08EL01557
Permite Description: UPGRADE: ELECTRICAL FROM 100-200 AMP (RES)
R1 ADD FEEDER & SUBPANEL IN LAUNDRY BUILDING
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2008 | ELECTRIC - SERVICE UPGRADE | N/A | Partial Approval | IVRS - Inspection :* 1) NEED TO CONNECT GROUND TO PANEL 2) NEED TO PUT ADDRESS ON PANEL 3) NEED ANTI-OXIDE COMPOUND ON ALL ALUMINUM CONDUCTORS 4) NEED TO BOND GAS AND WATER LINES 5) OWNER ON SITE, WILL MAKE CORRECTIONS PRIOR TO TEP RECONNECT AND FINAL INSPECTIONS 6) NEED ALL CIRCUITS IDENTIFIED FOR FINALS |
| 10/28/2008 | ELECTRIC - FINAL | N/A | Partial Approval | IVRS - Inspection :* 1) OWNER ADDING SUB PANEL TO S.E. BLDG GOING TO ADD THIS TO PRESENT PERMIT |
Completed Inspections
Permit Status: Expired
Permit Number: T08EL01557
Permit Description: UPGRADE: ELECTRICAL FROM 100-200 AMP (RES)
R1 ADD FEEDER & SUBPANEL IN LAUNDRY BUILDING
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2008 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER D. WALKER |