Permit: T08EL00149
Permit Details
Apply Date:
01/25/2008
Applicant:
JOSUE E SILVA
Description:
RECONNECT:ELECTRIC RESIDENCE R1 - Elec upgrade 100amps 3/4/08
Permit Reviews
Permit Number - T08EL00149
Permit Status: Expired
Permit Description: RECONNECT:ELECTRIC RESIDENCE
R1 - Elec upgrade 100amps 3/4/08
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/04/2008 | ELECTRICAL | 03/04/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T08EL00149
Permit Status: Expired
Permit Description: RECONNECT:ELECTRIC RESIDENCE
R1 - Elec upgrade 100amps 3/4/08
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 01/25/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T08EL00149
Permite Description: RECONNECT:ELECTRIC RESIDENCE
R1 - Elec upgrade 100amps 3/4/08
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2008 | ELECTRIC - SERVICE UPGRADE | N/A | Partial Approval | IVRS - Inspection :* |
| 03/20/2008 | ELECTRIC - RECONNECT | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED DETAILED PANEL DIRECTORY 2. INSTALL BREAKERS LISTED FOR USE IN CUTTER-HAMMER PANEL 3. CONNECT EQUIPMENT GROUND TO OLD PANEL 4. TIGHTEN ALL LOCK NUTS ON CONNECTORS 5. SEAL OPENING TOP OF OLD PANEL 6. VERIFY NOT SHARING NEUTRAL WITH SAME PHASE ON SPLIT BREAKERS 7. CUTTER-HAMMER SPLIT BREAKERS ARE FOR REPLACEMENT USE ONLY - NOT FOR NEW INSTALLS |
| 03/20/2008 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
Completed Inspections
Permit Status: Expired
Permit Number: T08EL00149
Permit Description: RECONNECT:ELECTRIC RESIDENCE
R1 - Elec upgrade 100amps 3/4/08
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2008 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER D. SANTACRUZ |