Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
07/29/2008
Applicant:
N/A
Description:
REPAIR FIRE DAMAGE:T08DV06409:REPLACE:2 200AMP DISCONNECTS
Contractors:
  • EMORY ELECTRICAL CONTRACTOR,*C

Permit Reviews

Permit Number - T08CM02600
Permit Status: Final
Permit Description: REPAIR FIRE DAMAGE:T08DV06409:REPLACE:2 200AMP DISCONNECTS
Start Date Submittal Complete Date Status  
07/29/2008 OTHER 10/15/2008 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T08CM02600
Permit Status: Final
Permit Description: REPAIR FIRE DAMAGE:T08DV06409:REPLACE:2 200AMP DISCONNECTS
Total Outstanding Activity Conditions - 1
Date Name
07/29/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T08CM02600
Permit Description: REPAIR FIRE DAMAGE:T08DV06409:REPLACE:2 200AMP DISCONNECTS
Total Completed Inspections - 3
Date Description Inspector Results Comments
08/04/2008 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection :
See detailed listing on site.| 999*
#6 GROUNDING CONDUCTOR IN SERVICE DISCONNECTS TO SMALL, SIZE PER 250.66 (#4) HAVE CONTR. ON SITE NEXT INSPECTION TO REMOVE GUTTER AND PANEL COVERS
08/04/2008 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection :*
RETURNED AFTER HRS. INSP. PER CONTR. REQ. PAID $150.00 CK#13757

CLEARANCE CALLED INTO TEP @ 4:03 P.M
KATHY AND MAP ROOM #150
08/04/2008 ELECTRIC - INTERMEDIATE DSANTACR Approved IVRS - Inspection :*

Documents

File Name Document Type  
None DOCUMENTS VIEW